35KV Digital High Voltage Wireless Phase Detector Precautions and Maintenance:
1. When performing frequency transmission calibration, the antenna must be installed first before calibration. The housing of the high voltage phase detector is made of polycarbonate and must be kept clean. Any dirt or moisture must be wiped off. After each use, wipe the instrument with a cloth dipped in a little silicone oil.
2. When not in use, the instrument must be properly stored in its case.
3. In low temperature environments (-10 degrees or lower), the instrument must be stored in a warm place as required. Batteries may fail due to cold.
4. The instrument should be tested before each use.
35KV Digital High Voltage Wireless Phase Detector Technical Features:
1. Screen display content: Wireless high voltage phase detector, different phase, same phase, frequency, X, Y, , , .
2. Power supply: The host uses rechargeable power, X and Y collectors use 5 AG13 batteries.
3. Auto power off: The host automatically powers off about 8 minutes after power on.
4. When contacting the strong electric field under test, the instrument will automatically alarm.
Technical Specifications:
1. Same phase qualitative: ≤15° is same phase
2. Accuracy: Self-calibration error ≤2°, field test: same phase error ≤8°, different phase error ≤13°
3. Sampling rate 3 times/second
4. Host power supply is 9V±2V
5. X and Y collector power supply voltage is 12V±3V
6. Host working current ≤7mA
7. X and Y collector working current ≤5mA
8. Visual range transmission distance between host and X, Y collectors is X≥150m, Y≥150m
9. Working environment: -35℃┉ 50℃ Humidity: ≤95%RH
10. Storage environment: -40℃┉ 55℃ Humidity: ≤95%RH
11. The AC voltage level measured by this product is 0.38KV┉500KV