Withstand Voltage of 10kV, 35kV Apparatus and Insulating Boots and Gloves



Insulating rod: 10KV---0.7m length-----45KV withstand voltage for 1 minute, 35KV---0.9m length----95KV withstand voltage for 1 minute.

Insulating gloves: High voltage---8KV withstand voltage for 1 minute, leakage current not greater than 9mA; low voltage---2.5KV withstand voltage for 1 minute, leakage current not greater than 2.5mA,

Insulating boots: 15KV withstand voltage for 1 minute, leakage current not greater than 7.5mA

For details, please refer to:GB/T 17622-2008 Live working-Insulating gloves (for use in live working at 35kV and below)

GB12011-2009 Foot protection - Electric insulating shoes