It is a special equipment designed and manufactured specifically for current load tests and temperature rise tests in electrical equipment testing in power departments and industrial and mining enterprises, such as various switches, current transformers, and other electrical equipment.
This product is small in size, light in weight, adopts an integrated structure, has stepless adjustment of output current, balanced current rise, large load variation range, uses 0.5-class current transformer, digital display, beautiful appearance, reliable operation, simple operation, and safety. It is an ideal equipment for current rise tests in industrial and mining enterprises.
Product Parameters:
◆ Rated capacity of current riser: 5KVA
◆ Rated capacity of voltage regulator: 5KVA
◆ Rated input voltage: 220V
◆ Rated input current: 22.7A
◆ Rated output current: 0-1000A
◆ Rated output voltage: 5V
◆ Structure form: integrated type
◆ Power supply phase: single phase
◆ Test accuracy: 1%
Operating Conditions:
◆ Working power supply: 220V ±10% 50Hz
◆ Ambient temperature: -10℃~+50℃
◆ The product should be placed in a place without gas vapor, chemical deposition dust, dirt, or other explosive media that seriously affect transformer insulation.
Working Principle:
◆ The instrument must be well grounded.
◆ After connecting the working power supply, turn on the switch, the red indicator light is on, press the start button, the green indicator light is on. Connect the output terminal to the test object, and the current riser is ready for current rise.
◆ Rotate the voltage regulator evenly clockwise, and pay attention to the output current indication on the operation panel to reach the required high current.
◆ During the test, once any abnormal phenomenon is found, cut off the power immediately, find out the cause, and then conduct the test again.
◆ After the test, the voltage regulator must be returned to zero, press the stop button to cut off the power, cut off the working power, and then remove the test wiring to ensure safety.
Precautions:
◆ For newly installed transformers and those not used for a long time, measure the insulation resistance between coils and between coils and ground with a 1500 megohmmeter before operation. Only when the resistance value is not lower than 0.5 megohm can they be used.
◆ During use, the current rise transformer and the operation panel must be reliably grounded to ensure safety.
◆ When in use, the current should be raised slowly and evenly, and excessive vibration should be avoided during transportation.
◆ The contact surface between the voltage regulator and the carbon brush should be kept clean, and wiped clean with cotton yarn dipped in 90% alcohol as appropriate.
◆ This equipment should be stored in a clean, ventilated, dry, and indoor place.