Technical Parameters of High Current Generator



Introduction:



The high current generator is essential equipment in various industries for electrical debugging where high current is required. It is applied in power plants, substations, electrical appliance manufacturing plants, and research and testing laboratories. It operates under short-time or intermittent duty. Increasing the current-carrying time can improve work efficiency and expand the testing range. It features small size, light weight, good performance, and easy maintenance.



The high current generator is specially designed and manufactured for electrical equipment tests in power departments and industrial and mining enterprises, such as current load tests and temperature rise tests for various switches, current transformers, and other electrical equipment. This series of high current generators adopts integrated or split structures depending on product volume and weight. It features stepless output current adjustment, balanced current rise, wide load variation range, reliable operation, simple operation, and safety. It is an ideal device for current rise or temperature rise tests in industrial and mining enterprises.



Technical Parameters of High Current GeneratorMain Features:



1. Load test, can be output instantaneously as required.

2. Stable output current, clear instrument indication, convenient for data recording and observation of the tested object.

3. Output current is divided into gears, each gear is smoothly adjustable, with flexible up and down control, and continuous and uniform adjustment.

4. Small size, light weight, flexible movement, and convenient operation, suitable for field use.



Technical Specifications:



1. Input power: AC: 220V-25A, 50Hz

2. Output current: AC: 1000A, 5V or 500A, 10V

3. Output current waveform distortion: ≤5%

4. 4 1/2 LCD digital display, range: 0~1000A, resolution: 0.1A,

accuracy: ±0.5%

5. Operating environment: temperature -10-40°C, relative humidity <80%

6. Dimensions: 402X232X245mm

7. Weight: 30Kg



Usage Methods and Precautions:



1. Connect the working circuit according to the electrical schematic diagram. The transformer casing, operation console, etc. must be properly grounded.



2. Connect the power supply, and the green indicator light on the operation console will turn on. Press the start button, the high current generator is ready, and the current booster waits for current rise.



3. Rotate the voltage regulator clockwise evenly, and pay attention to the output current indication on the operation console until the required high current is reached. To ensure testing accuracy, a standard ammeter can be connected in series at the instrument terminals.



4. During the test, if any abnormal phenomenon is found, cut off the power immediately, and then conduct the test after finding out the cause.



5. After the test, the voltage regulator must be returned to zero, press the stop button to cut off the power, and then disconnect the working power before removing the test wiring to ensure safety.