Product Aliases









Transformer characteristic comprehensive test bench, transformer characteristic test bench, transformer comprehensive test bench, transformer test bench, transformer electrical test bench, transformer comprehensive test bench


 



Product Introduction



    TLHG-203transformer comprehensive test bench can truly determine the no-load current, no-load loss, impedance voltage and load loss of power transformers, accurately measure the DC resistance and transformation ratio of power transformers, implement condition diagnosis, ensure safe operation, and provide reliable data for monitoring or repairing transformers. The transformer comprehensive test bench is suitable for power supply and distribution systems, power transformer manufacturers, industrial and mining enterprises and other units.

Product Features:

1. Transformer no-load, load, DC resistance, transformation ratio and polarity tests.
◇ The transformer no-load, load, DC resistance, transformation ratio and polarity tests are completed through the industrial computer.
◇ The transformer comprehensive test bench conducts comprehensive control and measurement monitoring of the entire circuit.
◇ The measured data is automatically processed by the microcomputer, and can be stored and printed as needed.
2. Power frequency withstand voltage test
◇ Since this test is a safety high-voltage test, in order to ensure the safety of test equipment and personnel, this test does not use the industrial computer to complete the test.
◇ Adopt electric control voltage regulation system. Automatic voltage rise and fall, digital display
◇ Zero position protection, overcurrent protection, overvoltage protection.
◇ High-voltage leakage current display and protection.
3. Induced withstand voltage test
◇ Since this test is a safety high-voltage test, in order to ensure the safety of test equipment and personnel, this test does not use the industrial computer to complete the test.
◇ Use a 150Hz medium frequency generator set to provide test power supply.
4. The transformer comprehensive test system consists of four parts
◇ Transformer comprehensive test bench used for each test unit and instrument monitoring data collection.
◇ Low-voltage control cabinet.
◇ Medium frequency generator set.
◇ Power frequency withstand voltage test.
5. The transformer comprehensive test bench consists of four major parts
◇ Industrial computer and data processing software system.
◇ Data collection system for each test unit.
◇ Power control and instrument monitoring system.
◇ Human-machine interface comprehensive system.


 



Product Parameters



1. Technical indicators of transformer characteristic tester:
  ◇ Voltage measurement range 1V—500V, current measurement range 100mA—5A, accuracy class 0.1.
  ◇ Power U*I, accuracy class 0.2.
  ◇ Working frequency 50Hz.
  ◇ Power factor 0.050--0.999, accuracy class 0.2.
  ◇ Frequency 45—65Hz, accuracy class 0.1.
2. Technical indicators of DC resistance tester:
  ◇ Measurement range: 0.01A: 1μΩ~2kΩ    1A: 1μΩ~20Ω
                  5A: 1μΩ~4Ω     10A: 1μΩ-2Ω
  ◇ Measurement accuracy: class 0.2, resolution: 1μΩ
3. Technical indicators of automatic transformation ratio tester:
  ◇ Transformation ratio measurement range: 1-10000
  ◇ Accuracy: class 0.2.
  ◇ Power supply: AC 220V±10%, 50Hz.
4. Technical indicators of current transformer
 ◇ Measurement range 100mA-200A.
 ◇ Accuracy class 0.05.
 ◇ Its transformation ratio is 5A, 10A, 20A, 50A, 100A, 200A six gears.
5. Technical indicators of induction voltage regulator
 ◇ Input voltage three-phase 400V.
 ◇ Output voltage three-phase 20V-650V.
 ◇ Output capacity 100KVA.
6. Technical indicators of 20kVA/50kV test transformer
 ◇ Rated capacity: 20kVA
 ◇ Input voltage: AC400V       
 ◇ Input current: 50A
 ◇ Output voltage: single-phase 50kV           
 ◇ Output current: 500mA
7. Technical indicators of 30kW/800V medium frequency generator
◇ Medium frequency generator
◆ Model: YR--8 wound rotor medium frequency generator
◆ Rated power: 30kW
◆ Rated voltage: 800V
◆ Nominal frequency: 150Hz
◆ Rated power factor: cosφ=0.8 lagging
◆ Number of phases: 3ph
◇ Motor
◆ Model: Y - 4 three-phase squirrel cage asynchronous motor
◆ Rated power: 22kW
◆ Rated voltage: 380V
◆ Rated frequency: 50Hz
◆ Number of poles: 4P
◆ Synchronous speed: 1480r/min
(Note: The above are the test configuration parameters for oil-immersed power transformers and dry-type transformers with voltage level 10kV/0.4kV/2500kVA and below, which can be customized according to the customer's test object and the required test items)