Main parameters of the automatic insulating boots (gloves) withstand voltage test device:
1. Input voltage: AC220V/50Hz
2. Capacity: 3kVA
3. High voltage: 0~30kV
4. High voltage current: 0~100mA
5. Number of test samples: 6 at a time
6. Measurement data: can display and print the voltage value and leakage current value of each tested sample
7. Overcurrent protection; overvoltage protection; custom time, voltage, leakage current values
8. LCD display, full Chinese menu operation, with printing
9. Measurement accuracy: voltage ±2% (±3 digits) current ±2% (±3 digits)
10. Weight: insulating boots (gloves) operation box 12Kg, power frequency withstand voltage test bench 60kg
Main features of the automatic insulating boots (gloves) withstand voltage test device:
1. Voltage, current, time data displayed on the same LCD screen with backlight, clear and intuitive reading.
2. Full Chinese interface, simple and clear operation, wide applicability.
3. Touch panel button operation, all functions can be set via buttons, improving product safety and reliability.
4. Combination of hardware and software anti-interference technology, stable performance, strong anti-interference.
5. This test device can test the leakage current of 6 channels simultaneously.
Test steps
1. Connect the control box power socket to 220V power supply and ground the grounding terminal.
2. Set the test time and overcurrent protection value.
3. Before turning on the power, return the voltage regulator to zero, close the knife switch, the disconnect button light is on, if alarm is needed, press the alarm switch, the alarm will sound and light. Press the start button, the start button light is on, and the alarm stops, indicating that it is powered on and waiting for voltage increase.
4. Rotate the voltage regulator handle clockwise at a constant speed to increase voltage, and closely monitor the control box instruments and the milliammeter of the water tank box.
5. If the milliammeter of the water tank box is abnormal, turn the milliammeter switch corresponding to the abnormal milliammeter to the "ON" position to protect the milliammeter from overcurrent damage.
6. When the required voltage is reached, turn on the time relay switch, and the time relay starts timing.