Product Description

Product Features


The ASCB1 series smart miniature circuit breakers are applied in low-voltage terminal distribution networks in industrial, commercial, civil buildings and infrastructure facilities within indoor buildings and similar places. Used with a smart gateway, they provide real-time monitoring of key electrical parameters of the power line, such as voltage, current, power, temperature, leakage, energy consumption, etc., and have functions such as remote control, abnormal warning, trip alarm, energy metering statistics, and fault location.

Detailed Introduction


I. Product Functional Features of Smart Miniature Circuit Breaker

① Real-time Monitoring: Used with a smart gateway, it can monitor key electrical parameters of the power line in real time, such as voltage, current, power, temperature, leakage, and energy consumption.

② Remote Control: It has remote control function, allowing users to control the switch anytime, anywhere.

③ Abnormal Warning: It has warning and protection function, which sends out warnings in time under abnormal conditions, effectively preventing the expansion of faults.

④ Short-circuit Protection: It has short-circuit protection function, which can quickly cut off the power supply in case of a short circuit to protect circuit safety.

⑤ Energy Metering Statistics: It can perform energy metering statistics, making it convenient for users to understand electricity usage.

⑥ Fault Location: It has fault location function, making it convenient for users to quickly find the fault point and carry out timely maintenance.

⑦ Small Size with Metering and Control: It is compact in size and has both metering and control functions, making it easy to install and use.

⑧ 0.1S Fast Power-off: It can achieve 0.1s fast power-off, effectively reducing fault losses.

II. Electrical Technical Parameter Table


Product Model

ASCB1-63

ASCB1LE-63

Number of Poles

1P/2P/3P/4P

2P/4P

Frame Size

63A

Rated Voltage

230V (1P/2P), 400V (3P/4P)

Rated Current

6A,10A,16A,20A,25A,32A,40A,50A,63A

Instantaneous Trip Type

C/D

Rated Short-circuit Breaking Capacity

6000A

Protection Functions

Overcurrent Protection

Default100% rated current warning, 110% rated current trip, threshold adjustable

Short-circuit Protection

Type C: 5-10 times rated current0.04 second circuit breaking protection

WeChat QR Code
💬
💬 Message

Hello! Have you found what you need? Contact us directly online!

Leave a Message for Consultation
Yangzhou Darui Electric Co., Ltd.
主营产品:Dielectric Loss Tester、Transformer Ratio测试仪、Loop Resistance Tester、高压None线核相仪、Insulation Resistance Tester、Partial Discharge Tester、Cable Fault Tester、DC Resistance Tester等。
☎ Phone: 18952707000(关经理)📞 Landline: 0514-88770377✉ Email: 195214804@qq.com
Verification Code
By submitting, you agree to ourTerms of ServiceandPrivacy Policy