Duct Heater
IV. Specifications
Single unit power from 2KW to 500KW series.
使用须知Notice:
In terms of control, a linkage device must be added between the fan and the heater to ensure that the heater starts only after the fan has started. After the heater stops, the fan must continue to run for at least 3 minutes to prevent the heater from overheating and being damaged. For single-circuit wiring, it must comply with NEC standards, and the current in each branch must not exceed 48A. The gas pressure heated by the duct heater generally does not exceed 0.3kg/cm2. If the pressure exceeds the above specification, please choose a circulation heater. The maximum temperature for low-temperature type heater gas heating does not exceed 160°C; for medium-temperature type, it does not exceed 260°C; for high-temperature type, it does not exceed 500°C.
Installation Form
Butt installation,
Plug-in installation,
Split installation,
Inlet installation