Product Aliases;
Transformer Characteristics Comprehensive Test Bench, Transformer Characteristics Test Bench, Transformer Comprehensive Test Bench, Transformer Test Bench, Transformer Electrical Test Bench, Transformer Comprehensive Test Bench
Product Introduction
TLHG-203Transformer Comprehensive Test Bench can truly determine the no-load current, no-load loss, impedance voltage, and load loss of power transformers, accurately measure the DC resistance and turns ratio of power transformers, implement condition diagnosis, ensure safe operation, and provide reliable data for monitoring or repairing transformers. The Transformer Comprehensive Test Bench is suitable for power supply and distribution systems, power transformer manufacturers, industrial and mining enterprises, and other units.
Product Features:
1. Transformer no-load, load, DC resistance, and turns ratio polarity tests.
◇ The no-load, load, DC resistance, and turns ratio polarity tests are completed through an industrial computer.
◇ The Transformer Comprehensive Test Bench provides comprehensive control and measurement monitoring for the entire circuit.
◇ The measured data is automatically processed by the microcomputer and can be stored and printed as needed.
2. Power frequency withstand voltage test
◇ Since this test is a safety regulation high-voltage test, to ensure the safety of test equipment and personnel, this test is not completed through an industrial computer.
◇ An electric control voltage regulation system is adopted. Automatic voltage rise and fall, digital display.
◇ Zero position protection, overcurrent protection, overvoltage protection.
◇ High-voltage leakage current display and protection.
3. Induced overvoltage withstand test
◇ Since this test is a safety regulation high-voltage test, to ensure the safety of test equipment and personnel, this test is not completed through an industrial computer.
◇ A 150Hz medium-frequency generator set provides the test power supply.
4. The transformer comprehensive test system consists of four parts
◇ The transformer comprehensive test bench used for each test unit and instrument monitoring data collection.
◇ Low-voltage control cabinet.
◇ Medium-frequency generator set.
◇ Power frequency withstand voltage test.
5. The transformer comprehensive test bench consists of four major parts
◇ Industrial computer and data processing software system.
◇ Data collection system for each test unit.
◇ Power control and instrument monitoring system.
◇ Human-machine interface comprehensive system.
Product Parameters
1. Technical indicators of transformer characteristics tester:
◇ Voltage measurement range 1V—500V, current measurement range 100mA—5A, accuracy class 0.1.
◇ Power U*I, accuracy class 0.2.
◇ Working frequency 50Hz.
◇ Power factor 0.050--0.999, accuracy class 0.2.
◇ Frequency 45—65Hz, accuracy class 0.1.
2. Technical indicators of DC resistance tester:
◇ Measurement range: 0.01A: 1μΩ~2kΩ 1A: 1μΩ~20Ω
5A: 1μΩ~4Ω 10A: 1μΩ-2Ω
◇ Measurement accuracy: class 0.2, resolution: 1μΩ
3. Technical indicators of automatic turns ratio tester:
◇ Turns ratio measurement range: 1-10000
◇ Accuracy: class 0.2.
◇ Power supply: AC 220V±10%, 50Hz.
4. Technical indicators of current transformer
◇ Measurement range 100mA-200A.
◇ Accuracy class 0.05.
◇ Its transformation ratios are six gears: 5A, 10A, 20A, 50A, 100A, 200A.
5. Technical indicators of induction voltage regulator
◇ Input voltage three-phase 400V.
◇ Output voltage three-phase 20V-650V.
◇ Output capacity 100KVA.
6. Technical indicators of 20kVA/50kV test transformer
◇ Rated capacity: 20kVA
◇ Input voltage: AC400V
◇ Input current: 50A
◇ Output voltage: single-phase 50kV
◇ Output current: 500mA
7. Technical indicators of 30kW/800V medium-frequency generator
◇ Medium-frequency generator
◆ Model: YR--8 wound-rotor medium-frequency generator
◆ Rated power: 30kW
◆ Rated voltage: 800V
◆ Nominal frequency: 150Hz
◆ Rated power factor: cosφ=0.8 lagging
◆ Number of phases: 3ph
◇ Motor
◆ Model: Y - 4 three-phase squirrel-cage asynchronous motor
◆ Rated power: 22kW
◆ Rated voltage: 380V
◆ Rated frequency: 50Hz
◆ Number of poles: 4P
◆ Synchronous speed: 1480r/min
(Note: The above are the test configuration parameters for oil-immersed power transformers and dry-type transformers with voltage levels of 10kV/0.4kV/2500kVA and below. They can be customized according to the customer's test object and required test items.)