DXW/PZ/J Type Self-Regulating Electric Heating Tape
Three parallel insulated copper stranded wires serve as power busbars. An electric heating wire is wound around the inner insulation layer, and this heating wire is connected to the power busbars AB-BC-CA-AB... in sequence at regular intervals (i.e., "heating pitch"), forming continuous parallel resistors between the three phases. When three-phase power is applied to the busbars, all parallel resistors heat up simultaneously, thus forming a continuous three-phase heating tape.
2. Product Specifications and Main Technical Indicators:
Normal insulation resistance ≥50MΩ per 100 meters
Insulation material: F46, maximum temperature resistance of heating tape: 250℃
Supply length: Maximum: 500M, Minimum: 50M
Dielectric strength: -2500V 50HZ/min
Explosion-proof mark: e ⅡT3, Explosion-proof certificate number: 289